Server Environment Monitoring System Sensors & Accessories

Sensors compatible with ENVIROMUX-MINI

Temperature/Humidity Combination Sensor

Temperature Sensor

TCP IP Temp/Humidity Probe

ENVIROMUX-TRH-xx
ENVIROMUX-TRH-xx
TCP IP Temp Probe

ENVIROMUX-T-xx
ENVIROMUX-T-xx
  • For use with ENVIROMUX-MINI.
  • Applications from 0°C and 40°C (32°F to 104°F) and 20% to 80% relative humidity.
  • High resistance to external influences on the cable due to digital output signal.
  • Accurate to within ±0.75°C (±1.35°F) and ±5% relative humidity.
  • Re-calibration is not necessary after initial set-up.
  • Available lengths: 0.9/1.8/3/7.6 meters.
  • Includes mounting hardware.
  • Regulatory approvals: CE, FCC, RoHS.
  • RoHS Compliant Temperature/Humidity Combination Sensor
RoHS compliant.
  • For use with ENVIROMUX-MINI.
  • Applications from 0°C to 40°C (32°F to 104°F).
  • High resistance to external influences on the cable due to digital output signal.
  • Accurate to within ±0.75°C (±1.35°F).
  • Re-calibration is not necessary after initial set-up.
  • Available lengths: 0.9/1.8/3/7.6 meters.
  • Includes mounting hardware.
  • Regulatory approvals: CE, FCC, RoHS.
  • RoHS Compliant Temperature Sensor RoHS compliant.

Liquid Detection Sensor

Door Contact Sensor

ENVIROMUX-LDx-y
ENVIROMUX-LDx-y
ENVIROMUX-M-DCS
ENVIROMUX-M-DCS
  • For warning of flooding.
  • 100% waterproof electronics.
  • Detects any conductive liquid.
  • Puddle: 1.53 cm diameter.
  • Detects liquid depth >0.25 cm.
  • Supports water sensor cable lengths from 0.3 to 305 meters.
  • Supports 2-wire cable lengths from 1.52 to 30.5 meters.
  • Regulatory approvals: CE, FCC, RoHS
  • RoHS Compliant Liquid Detection Sensor
RoHS compliant.
  • Monitors access with a magnetic bridge sensor, which responds to any magnetic material (no special inserts necessary).
  • Can also be used for monitoring side wall and covers.
  • Includes mounting hardware.
  • For normally closed circuit connection.
  • 2-wire interface.
  • Screw terminal.
  • Wide actuating gap, approximately 25mm.
  • Dimensions WxDxH (mm): 13x13x51 (Switch), 13x13x51 (Magnet).
  • RoHS Compliant Door Contact Sensor
RoHS compliant.

Humidity Sensor

Smoke Detector

TCP IP Humidity Probe

ENVIROMUX-RH-xx
ENVIROMUX-RH-xx
ENVIROMUX-TDS
ENVIROMUX-SDS-PA
  • For use with ENVIROMUX-MINI.
  • Applications from 20% to 80% relative humidity at temperatures between 0°C and 40°C.
  • High resistance to external influences on the cable due to digital output signal.
  • Accurate to within ±5% relative humidity.
  • Re-calibration is not necessary after initial set-up.
  • Available lengths: 0.9/1.8/3/7.6 meters.
  • Includes mounting hardware.
  • Regulatory approvals: CE, FCC, RoHS
  • RoHS Compliant Humidity Sensor
RoHS compliant.
  • For warning of smoke.
  • Built-in 57° C (135° F) thermal heat sensor.
  • Includes mounting hardware.
  • Photoelectric smoke detector.
  • Screw terminal.
  • Includes 9V/1A power supply.
  • Regulatory approvals: UL

Emergency/Panic Button

Temperature Sensor, Extended Range

ENVIROMUX-EBS
ENVIROMUX-EBS
ENVIROMUX-IND-xx
ENVIROMUX-T-IND-xx
  • Sends activation signal when button is pressed.
  • For normally closed or normally open circuit connections.
  • 2-wire interface.
  • Screw terminal.
  • Dimensions WxDxH (mm): 10x23x76
  • RoHS Compliant Emergency/Panic Button
RoHS compliant.
  • For use with ENVIROMUX-MINI-IND.
  • Applications from 0°C and 75°C (32°F to 167°F).
  • High resistance to external influences on the cable due to digital output signal.
  • Accurate to within ±1.25°C (±2.25°F).
  • Re-calibration is not necessary after initial set-up.
  • Available lengths: 0.9/1.8/3/7.6 meters.
  • Dimensions WxDxH (mm): 50.8x63.5x25.4
  • Includes mounting hardware.
  • Regulatory approvals: CE, FCC, RoHS
  • RoHS Compliant Temperature Sensor, Extended Range
RoHS compliant.

Tamper Switch

Air Flow Monitor

ENVIROMUX-TDS
ENVIROMUX-TDS
ENVIROMUX-AFM - Air Flow Monitor
ENVIROMUX-AFM
  • Sends activation signal when tamper switch is released.
  • Normally closed contact when depressed.
  • Dimensions (mm): inner diameter: 20, outer diameter: 23, height: 74
  • 2-wire interface.
  • Reliable mechanical solution for monitoring
    air flow.
  • Reacts to any condition causing insufficient flow of air such as malfunctioning cooling fan, increased friction, or physical blockage.
  • Can be used for direct monitoring of a cooling fan.
  • Dimensions WxDxH (mm): 34x17.5x7.5
  • Switch contact is closed when air flow is >2.5 m/s.
  • Connection: 2x single strand AWG26, length 0.5 m.
  • Available Lengths: 0.5/3/15.2/30.5/61/121.9/182.9/243.8/304.8 meters
  • Regulatory approvals: RoHS

GSM Modem

Power Over Ethernet Adapter

ENVIROMUX-GSM GSM Modem
ENVIROMUX-GSM-P
View Application Note How to: Access the IMEI Number of the GSM Modem
ENVIROMUX-POE Power Over Ethernet
ENVIROMUX-POE
View Application Note Application Note: ENVIROMUX-MINI Powered Over Ethernet
  • Sends SMS text messages to a pager or cell phone when a sensor goes out of range of a configurable threshold.
  • GSM modem with antenna built into system.
  • Convenient push-push SIM card holder
    • Mini SIM card supporting SMS messaging required (not included)
  • Protocols: AT commands
  • Supports one configurable authorized phone number for sending SMS text messages.
  • Auto PIN feature, no need to enter SIM card PIN after restart
  • Quad band: 850/900/1800/1900 MHz
  • SMS: Text mode
  • Power: 110 or 220 VAC at 50 or 60 Hz via AC adapter.
  • Regulatory Approvals: CE
  • Enables ENVIROMUX-MINI to be powered over Ethernet connection.
  • Eliminate the need to place ethernet-enabled devices near power outlets, giving more freedom of placement.
  • Supply Power and Data up to 91 meters using standard Ethernet cabling.
  • Outputs Power on an attached DC power cable, and Data on an attached Ethernet cable.
  • Ethernet Pin Usage:
    • Data: 1,2,3,6
    • Power: 4,5,7,8
  • No tools or software necessary for installation.
  • Overload and short circuit protection.
  • Standards: 802.3af
  • Dimensions WxDxH (mm): 76x83x45
  • Maximum power output: 5VDC @ 2.4A.
  • Regulatory approvals: RoHS, FCC, CE

Sensor Cables

DC Voltage Detector

ENVIROMUX-2W-xx
ENVIROMUX-2W-xx
ENVIROMUX-DCVD-24-515M
ENVIROMUX-DCVD-24V-M
  • 2-wire sensor cable.
  • Use to connect dry contact sensors to the ENVIROMUX-MINI.
  • Available lengths: .9/1.8/3/7.6/15.2/30.5 meters
  • RoHS Compliant Sensor Cables
RoHS compliant.
  • Measurement range: detects voltage from 24-36 VDC.
    • Contacts remain closed between 26-36 VDC
    • Contacts open when monitored voltage drops below 24 VDC
  • Measurement indication: Alarm or Normal.
  • Sensor type: open/closed contact switch.
  • Includes 6-foot 2-wire cable to connect to the ENVIROMUX-MINI.
  • Attached 3-foot power cord with tinned leads on 3 wires.
  • For use with ENVIROMUX-MINI purchased on or after 11/1/2007.
  • Regulatory approvals: RoHS
  • RoHS Compliant Power Converter
RoHS compliant.

3G Serial Modem

AC Voltage Detector

ENVIROMUX-3G 3G Serial Modem
ENVIROMUX-3G
RoHS Compliant Power Converter
ENVIROMUX-2W-xx
ENVIROMUX-ACVD-515M
ENVIROMUX-ACVD-515
ENVIROMUX-ACVD-C14M
ENVIROMUX-ACVD-C14


RoHS Compliant Power Converter
  • Sends SMS text messages to a cell phone when a sensor goes out of range of a configurable threshold.
  • Removable antenna.
  • Supports third generation (3G) digital cellular standards.
  • Convenient push button SIM card holder.
    • Mini SIM card supporting 3G SMS messaging required (not included)
  • Protocols: AT commands
  • Supports one configurable authorized phone number for sending SMS text messages.
  • Tri-band UMTS (HSDPA): 850/1900/2100 MHz
  • Quad band EDGE/GPRS/GSM: 850/900/1800/1900 MHz
  • Includes 12V/1A power supply.
  • Measurement range: detects voltage from 50 to 250 VAC.
  • Measurement indication: Alarm or Normal.
  • Sensor type: open/closed contact switch.
  • Attached 0.9 meter power cord.
    • ENVIROMUX-ACVD-515M: Standard US 120V 15A NEMA 5-15 plug (When using with ENVIROMUX-MINI that was purchased before 11/1/2007, use part number ENVIROMUX-ACVD-515)
    • ENVIROMUX-ACVD-C14M: Universal 250V IEC C14 socket (When using with ENVIROMUX-MINI that was purchased before 11/1/2007, use part number ENVIROMUX-ACVD-C14)
  • Regulatory approvals: CE, RoHS.