The Server Environment Monitoring System monitors critical environmental conditions, such as temperature, humidity, liquid presence, motion, intrusion, and vibration. When a sensor goes out of range of a configurable threshold, the system will notify you via email, LEDs, alarm beacon, web page, network management (SNMP), and SMS messages (via external GSM modem).
The system includes three internal sensors: temperature, humidity and power. It also supports 16 external configurable sensors and eight digital input sensors.
- Monitor and manage server room environmental and security conditions over IP.
- Create alarm signals with customized input parameters.
- Four output relays for control of external devices.
- Relays activate upon alarm or via the user interface.
- Supports IP network video camera.
- Live view of a facility from anywhere, anytime.
- Seamlessly integrate into the ENVIROMUX.
- Up to eight cameras can be associated with each ENVIROMUX.
- One integrated view - see different Web cameras side-by-side with physical and environmental parameters.
|
- Monitor (ping) up to 64 IP network devices.
- Alerts are sent if devices are not responding.
- Provides power supply for all sensors.
- Internal battery backup.
- Alerts are sent when there is a power outage and when power returns.
- Available sensors include: temperature, humidity, smoke, water, glas break, motion, vibration, 4-20mA converter, voltage detector, and more.
- Available with optional dual power for connection to two separate power sources.
- Up to four units can be used together to increase the number of sensors connected.
- Connect the units using CAT5 expansion cables.
- Uses a single Web interface for all systems connected.
- 1RU rack mount case is standard.
- Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.
|
 |
1. Power Port
- 110 or 230 VAC at 50 or 60 Hz via IEC connector.
- Connection for Earth Ground.
- Fuse protection.
- Optional dual power (not shown)
- 110 or 230 VAC at 50 or 60 Hz via IEC connector.
- If the first power source fails, the unit will automatically, without interruption, switch over to the second power source before switching to the battery backup.
2. RJ45 Sensor Ports- Sixteen RJ45 modular jacks for connecting NTI temperature, humidity, temperature/humidity, liquid detection, smoke detection, glass break, vibration and motion sensors.
3. Digital Inputs
- Screw terminals.
- Input voltage: 0 V DC to +25 VDC.
- Provides +12 V DC, 50 mA.
- Fuse protection.
4. Output Relays
- Screw terminals.
- Potential-free relay switch contacts.
- Maximum switching load: 0.5A at 100VAC, 1A at 30VDC
5. Beacon Port
- Screw terminals.
- Provides +12 V DC, 180 mA to supply an alarm beacon.
- Fuse protection
6. Siren Port
- Screw terminals.
- Provides +12 V DC, 130 mA to supply a siren.
- Fuse protection
7. Expansion Ports
- RJ45 connectors.
- A maximum of 4 systems can be cascaded to increase the number of sensor ports.
- Uses a single Web interface for all systems connected.
8. Console Port
- One female DB9 RS232 serial port for terminal access.
9. AUX Port
- One male DB9 RS232 serial port for controlling and monitoring external equipment, such as a GSM modem.
- GSM modems supported: Enfora GSM1218, MultiTech MTCBA-G-F2, Wavecom Fastrack M1306
10. AUX Power Port
- Provides +12 VDC, 150 mA.
- Fuse protection
11. Ethernet Port
- One 10/100 Base-T Ethernet port with RJ45 Ethernet connector.
| Protocols
- HTTP, SNMP V1/V2c, SMTP, TCP/IP, Syslog, SNTP
- Supports local authentication, SSL.
- Operates and configures via HTTP/HTTPS web page, Telnet or RS232 interface.
- Alerts are sent using email, SMS messages and/or SNMP traps when any monitored environmental condition exceeds a user-specified range.
- Alerts are posted in message log, which is accessible through Web user interface. The log can be downloaded as a tab-delimited plain text file.
- Sends notifications of alerts to a maximum of 17 email addresses, SNMP addresses and/or cell phone numbers. The users can configure the schedule when they will be alerted
Internal Temperature Sensor
- Applications from 0ºC to 40ºC (32°F to 104°F).
- Accurate to within ±0.75ºC (±1.35°F).
Internal Humidity Sensor
- Applications from 20% to 80% relative humidity at temperatures between 0ºC to 40ºC (32°F to 104°F).
- Accurate to within ±5% relative humidity.
Internal Power Sensor
- Measures mains voltage: 0 to 255 VAC
- Measures battery voltage: 0 to 20 VDC
- Alerts are sent when there is a power outage and when power returns.
Back-up Battery
- Rechargeable sealed lead-acid battery.
- Provides back-up for one hour.
Dimensions
Environmental
- Operating temperature: 0°C to 38°C (32°F to 100°F).
- Storage temperature: -30°C to 60°C (-22°F to 140°F).
- Operating and Storage Relative Humidity: 17 to 90% non-condensing RH.
Regulatory Approvals:
Warranty
|
|

|
- Full configuration via Web-page
- Configure sensor thresholds and timing, alarm methods, alert formats and system data log.
- View current sensor values and alert status.
- All sensors connected to the ENVIROMUX-SEMS can be viewed on one summary page.
- View entries stored in the system data log.
- The log can be downloaded as a tab-delimited plain text file.
- Configure IP information (address, subnet mask, default gateway, DNS, etc.) and user administrative settings.
- Administrate up to 16 users plus a root administrator.
- Permissions, schedule and alert methods are configurable for each user.
- Up to 8 users can access the web page at one time.
RS232 Control
- Display and configure network settings (IP address, subnet mask, default gateway, DNS, SMTP, etc.), Enterprise settings, and time settings.
- View current values and alert statuses for sensors/digital inputs/IP devices.
- Configure SNMP
- Serial baud rate: 9,600 to 115,200bps.
- Data format: 1 start bit, 8 data bits, no parity, 1 stop bit.
Telnet
- Display and configure network settings (IP address, subnet mask, default gateway, DNS, SMTP, etc.), Enterprise settings, and time settings.
- View current values and alert statuses for sensors/digital inputs/IP devices.
- Configure SNMP
- Security is ensured by password.
|
Network Operation
- When the system is integrated into a local network, the following functions are available:
- SNMP support, allowing integration into network management platforms.
- Updating the system firmware.
Front Panel Interface
- LEDs indicate the following:
- "INT ALERT" (red) illuminates if an internal sensor exceeds a configurable threshold.
- "EXT ALERT" (red) illuminates if an external sensor exceeds a configurable threshold.
- "LOW BAT" (red) illuminates when the backup battery is low.
- "CHECK LOG" (yellow) illuminates when a message is posted to the log.
- "PWR" (green) illuminates when the device is powered.
- LED Flashes when the unit is in backup mode.
Sensor Data Graphs
|