ENVIROMUX-ACVD-515
ENVIROMUX-ACVD-C14
 |

ENVIROMUX-S60VDC
|
- Measurement range: detects mains voltage from 50 to 250 VAC.
- Measurement indication: Alarm or Normal.
- Sensor type: open/closed contact switch.
- Includes 1.8 meter 2-wire cable to connect to the ENVIROMUX-SEMS-16.
- Attached 0.9 meter power cord.
- ENVIROMUX-ACVD-515: Standard US 120V 15A NEMA 5-15 plug
- ENVIROMUX-ACVD-C14: Universal 250V IEC C14 socket
- Regulatory approvals: CE, RoHS
|
- Monitors up to two DC voltages: -60VDC ~ 0VDC or 0VDC ~ 60VDC
- Connector: Screw Terminal, 5-position
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Includes Mounting Hardware
- Regulatory approvals: CE, RoHS
|
ENVIROMUX-ACLM-P12 ENVIROMUX-ACLM-P8
 |

ENVIROMUX-ACLM-V
|
- Reports AC Voltage, Frequency, Power, and Current.
- Monitors Power from one AC inlet to one AC outlet, between 50~250VAC and 47~63Hz.
- Monitors the number of swells, sags, and spikes.
- Includes Relay with configurable disconnect settings: threshold reboot, or manual reboot.
- Outlet Max load rating:
- ENVIROMUX-ACLM-P12 (US/Canada):
12A rated load, 15A maximum.
- ENVIROMUX-ACLM-P8 (Euro/UK):
8A rated load, 10A maximum.
- Capable of measuring current surges to 60A.
- User defined minimum and maximum voltage and power thresholds.
- Capable of detecting user selected spike events with a peak greater than 50V, 250V, 500V, or 1KV.
- Supports CAT5/5e/6 cable up to 305 meters. (not included).
- Regulatory approvals: CE, RoHS
|
- Reports AC Voltage and Frequency.
- Monitors AC voltage and frequency on two AC inlets between 50~250VAC and 47~63Hz.
- Monitors the number of swells, sags, and spikes.
- User defined minimum and maximum voltage thresholds.
- Capable of detecting user selected spike events with a peak greater than 50V, 250V, 500V, or 1KV.
- Supports CAT5/5e/6 cable up to 305 meters. (not included).
- Regulatory approvals: CE, RoHS
|

ENVIROMUX-PT1M-208-0800
ENVIROMUX-PT3M-208-0800
ENVIROMUX-PT3S-480-0100
Application Note: 3-Phase Power Transducer Application
|

ENVIROMUX-PT3-600 |
- Monitors and reports kW real power of any 3 phase circuit, such as the power a building consumes.
- Split-core design allows installation of CT without disconnecting conductor.
- Color coded CT and voltage leads.
- Smart electronics in sensors automatically detect phase reversal.
- Input primary voltage: 208/240 or 480 VAC RMS
- Number of phases monitored: one or three
- Balanced Loads: one CT model (assumes single reading represents all phase currents)
- Unbalanced Loads: three CT model, one black, red, and yellow.
- Frequency: 50/60Hz
- Maximum primary current: Up to 2400 amps continuous per phase
- Accuracy: +/- 1%
- Output: 4-20mA
- Supply power (current loop): 9-30VDC; 30mA max.
- Requires the ENVIROMUX-S420MA to operate.
- Caution: sensors tie directly into the line; should be installed by qualified electricians only.
- Make sure electrical service is disconnected before making any electrical connections.
| ENVIROMUX-PT1M-208-0800 |
208/240 |
800 |
Single Medium |
| ENVIROMUX-PT3M-208-0800 |
208/240 |
800 |
Three Medium |
| ENVIROMUX-PT3S-480-0100 |
480 |
100 |
Three Small |
|
- Monitors and reports voltage of any 3 phase circuit.
- Remotely detect blown fuses or tripped circuit breakers.
- Three 600VAC inputs, three 4-20mA outputs.
- Inputs and outputs isolated from one another.
- Frequency: 50/60Hz
- Maximum primary current: 600 volts
- Accuracy: ± 0.25% F.S. @60Hz
- Output: 4-20mA
- "Zero" adjustment for accurate 0VAC reading, and "Calibration" adjustment for frequency and voltage level.
- Powered by the ENVIROMUX-S420MA.
- Regulatory approvals: UL, CUL, CE
- Requires two ENVIROMUX-S420MA to monitor three phases.
- Caution: installation should be performed by qualified electricians only.
- Make sure electrical service is disconnected before making any electrical connections.
|

ENVIROMUX-S420MA

|

ENVIROMUX-PWR-RLY-15A
ENVIROMUX-PWR-RLY-20A
 |
- External RJ45 device monitors up to two 4-20mA analog sensors
- Supports ISA Type 2, ISA Type 3, and ISA Type 4 sensors.
- Resolution: 100mA
- Accuracy: 0.5% of full scale
- Provides 18VDC, 25mA for each sensor
- Connector: Screw Terminal, 8-position.
- Supports CAT5/5e/6 cable up to 305 meters. (not included)
- Includes Mounting Hardware
- Powered by ENVIROMUX-SEMS-16.
- Regulatory approvals: CE, RoHS.
- Compatible with ENVIROMUX-SEMS-16 only.
|
- Use with ENVIROMUX-SEMS-16 to remotely turn off the power of an AC powered device.
- Remotely reboot non-responsive computer systems.
- Two AC power receptacles.
- Load capacity:
- ENVIROMUX-PWR-RLY-15A: 15A at 120VAC.
- ENVIROMUX-PWR-RLY-20A: 20A at 120VAC.
- Dimensions WxDxH (mm): 96.5x50.8x139.7
- The baseplate is 133 mm square.
- Regulatory approvals: TUV
|
ENVIROMUX-2W-xx
 |
|
- 2-wire sensor cable.
- Use to connect dry contact sensors to the ENVIROMUX-SEMS-16.
- Available lengths: .9/1.8/3/7.6/15.2/30.5 meters
- Regulatory approvals: RoHS, UL
|
|