TCP IP Temp Probe

ENVIROMUX-STS
 |
TCP IP Humidity Probe
 ENVIROMUX-SHS
 |
- Applications from 0°C to 50°C (32°F to 122°F).
- Accurate to within ±0.5°C (±0.9°F).
- High resistance to external influences on the cable due to digital output signal.
- Re-calibration is not necessary after initial set-up.
- RJ45 connector.
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-SEMS-16
and SERIMUX-S-x only. |
- Applications from 20% to 80% relative humidity at temperatures between
0°C to 40°C (32°F and 104°F).
- Accurate to within ±5% relative humidity.
- High resistance to external influences on the cable due to digital output signal.
- Re-calibration is not necessary after initial set-up.
- RJ45 connector.
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-SEMS-16
and SERIMUX-S-x only. |
TCP IP Temp/Humidity Probe

ENVIROMUX-STHS
 |
TCP IP Temp/Wide Range Humidity Probe

ENVIROMUX-STHS-99
 |
- Applications from 0°C to 50°C (32°F to 122°F) and 20% to 80% relative humidity.
- Accurate to within ±0.5°C (±0.9°F) and ±5% relative humidity.
- High resistance to external influences on the cable due to digital output signal.
- Re-calibration is not necessary after initial set-up.
- RJ45 connector.
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-SEMS-16
and SERIMUX-S-x only. |
- Applications from 0°C to 50°C
(32°F to 122°F)
- Accurate to within ±1°C (±2°F)
- 20% to 80% relative humidity, ±3%
- 10% to 90% relative humidity, ±4%
- 0% to 99% relative humidity, ±5%
- High resistance to external influences on the cable due to digital output signal.
- Re-calibration is not necessary after initial set-up.
- RJ45 connector.
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-SEMS-16
and SERIMUX-S-x only. |

ENVIROMUX-SHS-PLT |

ENVIROMUX-STHS-PLT-xxx |
- NIST traceable calibration accurate to within ±1% from 10% to 80% relative humidity at 25°C to 35°C (77°F to 95°F).
- Two-point field calibration.
- Output: 4-20mA DC = 0% to 100% RH.
- Requires the ENVIROMUX-S420MA to operate.
|
- Available temperature ranges:
- ENVIROMUX-STHS-PLT-120: -6°C to 48°C (20°F to 120°F).
- ENVIROMUX-STHS-PLT-140: -28°C to 60°C (-20°F to 140°F).
- ENVIROMUX-STHS-PLT-180: -1°C to 82°C (30°F to 180°F).
- Temperature accurate to within ± 1.50%.
- NIST traceable calibration accurate to within ±1% from 10% to 80% relative humidity at 25°C to 35°C (77°F to 95°F).
- Uses a platinum RTD for precision temperature compensation.
- Sensing element: 1000W platinum; 2 lead resistance thermometer, .00385 TCR
- Two-point field calibration.
- Output: 4-20mA DC = 0% to 100% RH.
- Requires the ENVIROMUX-S420MA to operate.
|
 ENVIROMUX-STHS-WLM ENVIROMUX-STHS-DCT
| 
| ENVIROMUX-STSP-xx |
 |
|
- Combines excellent stability with easy installation and reliable operation.
- Wall Mount ENVIROMUX-STHS-WLM: Applications from -5°C to 55°C (23°F to 131°F)
- Duct Mount ENVIROMUX-STHS-DCT: Applications from -10°C to 60°C (14°F to 140°F)
- Temperature accurate to within ±0.3°C (±0.54°F)
- Relative Humidity accurate to better than ±3% from 10% to 90% relative humidity at 20°C (68°F).
- Re-calibration is not necessary after initial set-up.
- Insensitive to dust and most chemicals.
- Regulatory Approvals: CE, RoHS
- Requires the ENVIROMUX-S420MA to operate.
|
- Mount to the outside of a thin walled steel, copper, or aluminum pipe (up to 1/4" wall).
- Copper contact transmits surface temperature to thermal sensor.
- Weatherproof enclosure designed to IP67 specifications.
- Applications from -40°C to 85°C
(-40°F to 185°F).
- Accurate to within ±0.5°C (±1.0°F).
- Response time: <1 minute for temperature changes of ±2°F.
- High resistance to external influences on the cable due to digital output signal.
- Re-calibration is not necessary after initial set-up.
- MTBF: 1,942,123 hrs.
- Self centering mounting bracket available for 1-3" (44-76 mm) diameter pipe, and 3-6.5" diameter pipe (included).
- Included adjustable cable ties secure mounting bracket to pipe.
- Available lengths for attached CAT5e cable: 1/10/50/100/200/400/600/800/1000 feet (0.3, 3.0, 15.2, 30.5, 61, 122, 183, 244 meters).
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- Regulatory approvals: CE, RoHS.
- Compatible with ENVIROMUX-SEMS-16 and SERIMUX-S-x only.
|

| ENVIROMUX-STS-O |
 |
|
ENVIROMUX-SDS |
- Applications from -40°C to 85°C
(-40°F to 185°F).
- Accurate to within ±0.5°C (±0.9°F).
- Weatherproof enclosure designed to IP67 specifications.
- High resistance to external influences on the cable due to digital output signal.
- Re-calibration is not necessary after initial set-up.
- Quick release waterproof RJ45 connector.
- Supports CAT5/5e/6 cable up to 1,000 ft. (not included).
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- MTBF: 1,942,123 hrs.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-SEMS-16 and SERIMUX-S-x only.
|
- For warning of smoke.
- Built-in 57° C (135° F) thermal heat sensor.
- Includes mounting hardware.
- Connect to RJ45 or digital input sensor ports.
- Supports CAT5/5e/6 UTP or STP cables.
- Photoelectric smoke detector.
- Screw terminal
- To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
- Maximum cable length: 305 meters
- Powered by ENVIROMUX-SEMS-16.
- Regulatory approvals: UL
|

| ENVIROMUX-SDS-CE |
 |
|

| ENVIROMUX-LDSx-y |
 |
Application Note: Detect Conductive Liquids in a Server Room |
- For warning of smoke.
- Smoke sensitivity: 0.98-2.4%/ft.
- Built-in 57° C (135° F) thermal heat sensor.
- Applications from 0°C to 50°C
(32°F to 122°F).
- Includes mounting hardware.
- Connect to RJ45 or digital input sensor ports.
- Supports CAT5/5e/6 UTP or STP cables.
- Photoelectric smoke detector.
- Screw terminal
- To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
- Maximum cable length: 1,000 ft
- Powered by ENVIROMUX-SEMS-16.
- Regulatory approvals: CE, RoHS
|
- For warning of flooding.
- Detects liquid depth >0.25 cm.
- Minimum puddle: 1.53 cm diameter.
- 100% waterproof electronics.
- Detects any liquid, except deionized water.
- RJ45 connector.
- Supports CAT5/5e/6 cable up to 305 meters (not included).
- Supports water sensor cable lengths from 0.3 to 305 meters.
- Supports 2-wire cable lengths from 1.52 to 30.5 meters.
- Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.
- Regulatory approvals: CE, RoHS
- Compatible with ENVIROMUX-SEMS-16 and SERIMUX-S-x only.
|

ENVIROMUX-AV
Connected to Converter
ENVIROMUX-S5VDC |
 |
Application Note: Measure Air Velocity in a Server Room
Application Note: Air Velocity Sensor Placement in Air Duct |

ENVIROMUX-CMD
|
- Reliable sensor for measurement of air velocity.
- Requires the ENVIROMUX-S5VDC sensor converter to operate.
- Flow range: 0-10m/s
- Accuracy: ±5% of measuring value at 20°C (68°F).
- Dust resistant design.
- Includes mounting hardware.
- Regulatory approvals: RoHS.
|
- Continuous air monitoring.
- Pre-set alarm points alert at:
- 70 ppm after 60 to 240 minutes
- 150 ppm after 10 to 50 minutes
- 400 ppm after 4 to 15 minutes
- Flush or surface mount.
- Test functionality of electrochemical CO sensing cell.
- Connect to RJ45 or digital input sensor ports.
- Screw terminal
- To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
- LED indicators for operation status and system test.
- Powered by ENVIROMUX-SEMS-16.
- Regulatory approvals: UL
|

| ENVIROMUX-S420MA |
 |
|

| ENVIROMUX-S5VDC |
 |
|
- External RJ45 device monitors up to two 4-20mA analog sensors
- Supports ISA Type 2, ISA Type 3, and ISA Type 4 sensors
- Provides 18VDC, 25mA for each sensor
- Connector: Screw Terminal, 8-position.
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Includes Mounting Hardware
- Powered by ENVIROMUX-SEMS-16.
- Regulatory approvals: RoHS.
- Compatible with ENVIROMUX-SEMS-16 only.
|
- External RJ45 device monitors up to two linear DC sensors, 0VDC ~ 5VDC
- Provides 12VDC, 25mA for each sensor
- Connector: Screw Terminal, 8-position.
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Includes Mounting Hardware
- Powered by ENVIROMUX-SEMS-16.
- Regulatory approvals: RoHS.
- Compatible with ENVIROMUX-SEMS-16 only.
|
 ENVIROMUX-2W-xx
|
|
- 2-wire sensor cable.
- Use to connect dry contact sensors to the ENVIROMUX-SEMS-16.
- Available lengths (m): .9/1.8/3/7.6/15.2/30.5
- Regulatory approvals: RoHS, UL
|
|